Features
- Dissipating Energy Flow method using P, Q, V and θ from PMUs
- Oscillation detection range 0.1 to 25 Hz, in three frequency bands: 0.1–1 Hz, 1–10 Hz, 10–25 Hz (detection up to 25 Hz requires a PMU sampling rate above 50 Hz)
- Separate magnitudes and two pickup times per frequency band for alarm and disconnection
- Algorithm repeated every second on a 10-second data window
- Raw data stored from 10 seconds before to 30 seconds after each event
- Circuit breaker trip signal and SCADA output signals; remote on/off option
- Functionality tested with Transgrid test data
Functions
- Detect sub-synchronous oscillations in real time
- Locate the oscillation source
- Calculate oscillation frequency, magnitude and start time
- Alarm, generation curtailment and trip levels, fully customisable to utility requirements
- Trip signal to protection and data, alarm and control signals to SCADA